Pole Guards are installed before setting new poles to guard against accidental line contact. They also guard against pole contacts by personnel working insulating aerial buckets or on platforms. Pole Guards are made from orange, Type I ABS, cold weather, high impact thermoplastic. Salisbury Pole Guards feature the unique Air Gap design. Uniformly spaced dimples minimize the amount of surface area contacting the pole. This provides added insulation to keep electrical leakage to a minimum. When two pole guards are used to cover longer lengths, the Air Gap dimples nest together "locking" the two together with ample overlap. This is an exclusive feature to Salisbury Pole Guards. The Air Gap design also allows for air flow between it and the ...
Versa and Link Guards make use of air as well as the dielectric strength of plastic to provide total insulating value. Both guards have a 7" diameter and a hook shaped inner lip to keep the guard in place.
Versa Guards, with a voltage rating of 36.6 kV (guarded Ø to guarded Ø), are designed so that two guards can be coupled together to cover most 13 single and double arm, pin and post constructions. A lighter version (2389) of the standard 4.5' Versa Guard is available in a Type III ABS/PVC weather resistant material.
Link Guards, with a voltage rating of 72.5kV (guarded Ø to guarded Ø), have inner and outer shells that run full length to include male and female couple ends. Two guards connected ...
Lightweight Conductor Covers are ideal to cover long spans when weight is a consideration. They can be applied when wearing rubber gloves or with a fiberglass stick. Available with an eye for application with shotgun sticks. These covers have a voltage rating of 26.4 kV (guarded Ø to guarded Ø). The inside diameter is 2". This product can connect with Salisbury 1.5" I.D. Class 3 or 4 flexible cover-up equipment.
The 21826 Lightweight Conductor Cover is a six (6', 1.8m) foot, cover rated Class 4 (36.6 kV - guarded Ø to guarded Ø). It is applied using rubber gloves when following appropriate company work rules. The inside diameter is 3" making it useful on a wide range of conductor sizes.
Crossarm Guards are available in two different styles: the 1370 pin type and the 1371 post type. They are used to prevent tie wires from contacting crossarms during hot line operations. Two different tie downs are provided: a neoprene and a polypropylene rope. Both are secured in the slots provided in the eye fitting. The post type model has an automatic gap closer which covers the insulator slot opening over the end of the arm.
The Slide-On Crossarm Guard 736PH is applied by sliding the cover on to the arm from the end using the shotgun eye until the unit locks onto the insulator pins. The cover overlaps on top and has notches to ease application and removal.
Both of these guards are made from orange Type I ABS cold ...
Substation Cover-up and barrier equipment is used during routine maintenance where accidental contact may occur. This barrier equipment is often used where outages are difficult to reach and the occurrence of accidental contact is high. These covers may be applied with rubber gloves or hot sticks. These covers are made from Type I orange ABS plastic. This equipment is not intended for permanent or semi-permanent barrier or insulating applications. Use these covers to protect against accidental contact only. These covers are not to be left installed for extended periods of time especially when in contact with both a grounded and energized object.
Bus Guards are easily interlocked with each other. To interlock units determine the ...
The Universal Hot Cover is used to provide additional cover-up and clearances. This cover is made from orange Type I polyethylene plastic. The hot stick eye allows this cover to be placed and removed with a shotgun type clamp stick or with rubber gloves. To secure in place use the elastic tiedown cord. This cover can be used on overhead or underground energized cable terminators, potheads or while inverted, on lightning arrestors. This cover has a voltage rating of 26.4 kV (guarded Ø to guarded Ø).
The Pole Bracket and Insulator Base Cover guards against accidental contact with pole, bracket and insulator base during routine maintenance. It is made from an orange UV resistant Type I polyethylene plastic. The Grade 2 ...